Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.3.2.2 Cylinders Test shall be performed x 15 minute standing car test was performed and failed. A test shall be made with the car stopped and the system operating under normal operating pressure for a period of not less than 15 minutes. During this period, the car shall not lower more than 2 inches. Take corrective action and re-test. Note: The car dropped more than 2 inches.
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase 1 fire service key shall be removable in the "On" position. 9/20/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The car top light shall be operational. 11/8/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers The fire extinguisher in the elevator machine room is expired and shall be replaced or serviced. 7/2/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 7/27/2021