MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone is not working. Re-inspection required
|
11/18/2025
|
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
The elevator packing gland seeped an excessive amount of oil in testing. The packing gland shall be repaired or replaced. Reinspection required in 30 days.
|
6/15/2021
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
x
|
|
This elevator has an overspeed valve device installed and is now required to have a 5 year full load test performed. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Overspeed valve shall be tested and a reinspection is required.
|
|