A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
No
|
No
|
Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag.
|
|
|
A17.1-2016 : Elevators
|
2.5 - Housekeeping
|
8.6.4.9 Cleaning of Top of Cars
|
No
|
No
|
Car top shall be kept free of excess debris/dirt/lint.
|
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
No
|
No
|
Pit shall be kept dry. Remove rust from pit equipment , repair/replace as needed, apply rust prevention treatment to all pit steel, investigate/repair water leak
|
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
No
|
No
|
The machine room lights shall work.
|
11/21/2019
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
No
|
No
|
In car emergency lighting shall work.
|
11/21/2019
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
4/20/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
No
|
No
|
All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
4/20/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
No
|
No
|
An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
|
4/20/2021
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
No
|
No
|
NEC - Sump pump shall be on independent circuit separate from light switch.
|
5/29/2024
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
5/29/2024
|