MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provde a working phone line and have retested
|
7/15/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace the damaged heat detector in the pit.
|
8/30/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)7
|
|
|
Per NEC install a lockable 110 light disconnect to the car lights in the machine room
|
7/25/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
|
|
Add 2 hand grab rails above the existing pit ladderfrom the top up to at least 30 inches above the lower level floor landing.
|
7/25/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Remove the plastic pit cover and replace it with a metal cover that will hold 250lbs. .
|
7/25/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Cut a trench from the jack base which is lower than the pit floor to the sump pit to relieve the standing water.
|
7/25/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Repair or replace the pit light
|
8/30/2024
|