Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Provde a working phone line and have retested 7/15/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace the damaged heat detector in the pit. 8/30/2024
MO Minimum : Elevators (H) - Machine Rooms (H)7 Per NEC install a lockable 110 light disconnect to the car lights in the machine room 7/25/2020
MO Minimum : Elevators (I) - Pits (I)5 Add 2 hand grab rails above the existing pit ladderfrom the top up to at least 30 inches above the lower level floor landing. 7/25/2020
MO Minimum : Elevators (I) - Pits (I)8 Remove the plastic pit cover and replace it with a metal cover that will hold 250lbs. . 7/25/2020
MO Minimum : Elevators (I) - Pits (I)1 Cut a trench from the jack base which is lower than the pit floor to the sump pit to relieve the standing water. 7/25/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair or replace the pit light 8/30/2024