Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Provde a working phone line and have retested 7/15/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Must patch/replace missing Drywall to maintain Machine room enclosure and fire rating. (H)2
MO Minimum : Elevators (H) - Machine Rooms (H)7 No No Per NEC install a lockable 110 light disconnect to the car lights in the machine room 7/25/2020
MO Minimum : Elevators (I) - Pits (I)1 No No Cut a trench from the jack base which is lower than the pit floor to the sump pit to relieve the standing water. 7/25/2020
MO Minimum : Elevators (I) - Pits (I)5 No No Add 2 hand grab rails above the existing pit ladderfrom the top up to at least 30 inches above the lower level floor landing. 7/25/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Repair or replace the pit light 8/30/2024
MO Minimum : Elevators (I) - Pits (I)8 No No Remove the plastic pit cover and replace it with a metal cover that will hold 250lbs. . 7/25/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Must make Emergency Battery lowering devise operable. ( currenty dead battery). 8.6.1.6
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace the damaged heat detector in the pit. 8/30/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Must make emergency phone operable. 1.6