Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 3.10 - Hoistway construction 100 Path the holes in the wall between the machine room and the hoistway back to a 2 hour rated assembly 1/1/2024
A17.1-1996 : Elevators 1.12 - Car enclosure 204 Remove the display boards inside the elevator car , They can only project 1.5" and must have rounded corners and edges. 8/25/2021