Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide a code compliant MCP including onsite documents. 10/4/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 Clean the pit of oil, dirt, and debris. 10/4/2022
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an overspeed valve this is not sealed. A category 5 test shall be performed on or before the next annual inspection. The valve shall be tagged and sealed after a successful category 5 test. 10/4/2022
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x Door restrictor does not work. 10/4/2022
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone. 11/30/2022
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x When the car is outside the unlocking zone, the hoistway doors or car doors shall be so arranged that they cannot be opened more than 4 inches from inside the car. 11/30/2022