Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The current state operating certificate shall be posted in the machine room in a non-combustible frame.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals.
MO Minimum : Elevators (I) - Pits (I)5 Current pit ladder is beside non running unit. Unable to access pit. Provide means.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Current pit light switch is beside a non running unit. Unable to access switch. Provide means.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Remove scavenger oil line form the hydraulic oil tank and provide a code compliant means to collect oil in pit to record oil loss.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Sight guard missing from 1st floor hoist way door, replace.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The emergency car lighting is not operational.The fixture shall be repaired to operate. Reinspection required.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The elevator alarm bell inside the elevator is not working. Check and repair the alarm bell for proper operation and passenger safety. Reinspection required.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The car top inspection light doesn’t operate. Repair fixture for proper operation.
conversion conversion n/a No maintenance records on site 9/19/2018
conversion conversion n/a Car door reopening device shall work 9/19/2018
conversion conversion n/a Missing nonvision panels on hoistway doors 9/19/2018
conversion conversion n/a Current state operating certificate shall be displayed 9/19/2018
conversion conversion conversion - reinspect x Emergency phone shall work 5/28/2019
conversion conversion conversion - reinspect x Emergency light shall work 5/28/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x The hold feature on Phase 2 fire service shall work properly. 10/29/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x The door close feature on Phase 2 fire service shall work properly. 10/29/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x The photo eye shall be bypassed on Phase 2 fire service. 10/29/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x The smoke detector is obstructed with a rag. Remove the obstruction. 10/29/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x In car emergency phone shall work. 10/29/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting In car emergency lights shall work. 12/1/2020
MO Minimum : Elevators (A) - Hoistways (A)2 Sight guards missing on hoistway doors. 12/1/2020
MO Minimum : Elevators (A) - Hoistways (A)1 Sight guard is missing. 12/1/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 Patch the holes in the machine room wall. 12/1/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)6 Door reopening device (electric eye) does not work. 12/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Written maintenance control program shall be provided on site. 12/1/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Provide current state operating certificate in machine room. 12/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 12/18/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Not on site 4/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No fire extinguisher in machine room 4/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Provide MCP 4/1/2022
MO Minimum : Elevators (I) - Pits (I)5 Current pit ladder is beside non running unit. Unable to access pit. Provide means. 4/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Remove scavenger oil line. 4/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Provide code compliant means to collect oil in pit. 4/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Sight guard missing from 1st floor hoist way door, replace. 4/1/2022