MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals.
|
|
conversion
|
conversion
|
n/a
|
|
|
Car door reopening device shall work
|
9/19/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Car Emergency Light and Bell shall be repaired (bell muffled, light not working)
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Car lighting shall be guarded and ceiling panels repaired
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
Car top light shall be repaired.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current operating certificate shall be posted in machine room
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
|
|
Current pit ladder is beside non running unit. Unable to access pit. Provide means.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
|
|
Current pit ladder is beside non running unit. Unable to access pit. Provide means.
|
4/1/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Current pit light switch is beside a non running unit. Unable to access switch. Provide means.
|
|
conversion
|
conversion
|
n/a
|
|
|
Current state operating certificate shall be displayed
|
9/19/2018
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)6
|
|
|
Door reopening device (electric eye) does not work.
|
12/1/2020
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Emergency light shall work
|
5/28/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
12/18/2020
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Emergency phone shall work
|
5/28/2019
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Hole in hoistway (pit area) to machine room shall be sealed
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Holes in Overhead shall be sealed (previously a traction elevator)
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
In car emergency lights shall work.
|
12/1/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
In car emergency phone shall work.
|
10/29/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
Inspection key switch in COP shall be repaired
|
|
conversion
|
conversion
|
n/a
|
|
|
Missing nonvision panels on hoistway doors
|
9/19/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
No fire extinguisher in machine room
|
4/1/2022
|
conversion
|
conversion
|
n/a
|
|
|
No maintenance records on site
|
9/19/2018
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Not on site
|
4/1/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Patch the holes in the machine room wall.
|
12/1/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Phase2 sign is incorrect and shall be permanently covered (engraved in COP)
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
|
|
Pit ladder access is in non running unit. Unable to Access.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit Light switch is in a non running unit. Unable to Access.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit Shall be cleaned
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Provide code compliant means to collect oil in pit.
|
4/1/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Provide current state operating certificate in machine room.
|
12/1/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
Provide MCP
|
4/1/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Remove scavenger oil line form the hydraulic oil tank and provide a code compliant means to collect oil in pit to record oil loss.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Remove scavenger oil line.
|
4/1/2022
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
|
|
Sight guard is missing.
|
12/1/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Sight guard missing from 1st floor hoist way door, replace.
|
4/1/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Sight guard missing from 1st floor hoist way door, replace.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Sight Guard missing from 1st floor hoistway doors
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)2
|
|
|
Sight guards missing on hoistway doors.
|
12/1/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
The car top inspection light doesn’t operate. Repair fixture for proper operation.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The current state operating certificate shall be posted in the machine room in a non-combustible frame.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
The door close feature on Phase 2 fire service shall work properly.
|
10/29/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator alarm bell inside the elevator is not working. Check and repair the alarm bell for proper operation and passenger safety. Reinspection required.
|
5/8/2025
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The emergency car lighting is not operational.The fixture shall be repaired to operate. Reinspection required.
|
5/8/2025
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
The hold feature on Phase 2 fire service shall work properly.
|
10/29/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
The photo eye shall be bypassed on Phase 2 fire service.
|
10/29/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
The smoke detector is obstructed with a rag. Remove the obstruction.
|
10/29/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
Written maintenance control program shall be provided on site.
|
12/1/2020
|