Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)1 A17.1 - 8.11.2.1.3(t) - The distance from the face of the hoistway doors to the edge of the hoistway landing sills shall not be more than 5".
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)4 The car top shall be metal and shall sustain a load of 200 lbs. applied to any point on the car top. The car top shall be securely fastened and an emergency escape hatch provided.
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)6 A "No Passengers" sign shall be posted in the elevator cab.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods A fire extinguisher is required in the elevator machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The car top lighting shall be relocated to allow for proper clearance.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers There is no fire extinguisher in the machine room. An ABC type fire extinguisher with a current test tag shall be provided in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 5/9/2024
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room light shall be at least 10 fc and be guarded.
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key.
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The machine room lighting shall be not less than 10 foot-candles at floor level.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display the current state operating certificate in the machine room.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.