Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers x Fire extinguisher in machine room is expired, replace or have serviced. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars x Cartop still needs to be cleaned. Re-inspection required
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate x A copy of the current state operating certificate shall be on display in the machine room. Re-inspection required
MO Minimum : Elevators (I) - Pits (I)1 x Pit still needs to be cleaned. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A written copy of the MCP shall be kept in the machine room for each unit. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods x Re-install cover on cartop selector electrical box. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Hoistway dust covers still need to be re-installed and/or replaced as needed. Re-inspection required
conversion conversion conversion - reinspect x Car emergency telephone does not work. Needs to be programmed to a 24 hour source. 11/2/2018
conversion conversion n/a The elevator in the down direction will not stop at the designated floors. Goes straight to the bottom floor. 4/9/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The fire extinguisher in the machine room is expired. 4/9/2019
MO Minimum : Elevators (H) - Machine Rooms (H)3 Ceiling in machine room is damaged. 4/9/2019
MO Minimum : Elevators (H) - Machine Rooms (H)3 Water is entering machine room from damaged ceiling next to mainline disconnect creating a life and limb hazard. - Re-Inspection Required 4/9/2019
MO Minimum : Elevators (H) - Machine Rooms (H)1 Machine room door shall be self-closing. 4/9/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The car top shall be cleaned. 4/9/2019
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be cleaned. 4/9/2019
conversion conversion n/a Machine room door needs to be self closing and locking. 4/9/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The machine room fire extinguisher is expired and shall be re-certified or replaced. 8/21/2019
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-locking and self-closing. 8/21/2019
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean. 8/21/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No fire extinguisher in machine room. 12/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Cartop shall be kept clean. 12/1/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display updated state operating certificate in machine room. 12/1/2020
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept clean. 12/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone shall work. 12/18/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide MCP. 3/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers None. 3/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean car top. 3/1/2022
MO Minimum : Elevators (I) - Pits (I)1 Clean pit. 3/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Replace missing selector cover on car top. 3/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Replace missing dust cover hoist way door, top floor. 3/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces Observed black mold on ceiling,abate as needed. 3/1/2022
MO Minimum : Elevators (I) - Pits (I)1 Resubmit - Clean elevator pit 3/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Resubmit - Replace missing selector cover on car top 3/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Resubmit Replace missing dust cover on top floor hoistway door 3/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Door restrictor broken. 3/21/2022