MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
A light fixture in the elevator cab was not operational on the day of inspection. Repair light fixture to provide adequate lighting.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
There is no fire extinguisher in the machine room, as required. Provide an ABC type extinguisher of proper size for the room.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
The lighting in the elevator machine room is not sufficient. The lighting shall not be less than (10) foot candles at the floor level.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The elevator pit floor is covered in dust and debris. The pit shall be cleaned.
|
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
The belts on the hydraulic pump motor are mismatched and worn unevenly. Replace belts for a smooth operation of pump to motor.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean Elevator pit
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Pit access door shall be kept closed and locked
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces
|
|
|
Remove unnecessary materials from the machine room
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
x
|
|
Machine room door shall be kept closed and locked. Door shall be self closing and self locking
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Close hoistway wall penetrations
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Car emergency telephone does not work. Needs to be programmed to a 24 hour source.
|
2/20/2019
|
conversion
|
conversion
|
n/a
|
|
|
Fix the oil leak either on the valve or pump, or both.
|
4/19/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
No maintenance control program. Provide electrical prints for controller.
|
7/1/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
No fire extinguisher in machine room.
|
7/1/2020
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
Repair oil leaks under the tank.
|
7/1/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
12/18/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Need fire extinguisher in machine room
|
9/3/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Change Fire Service Phase II key switch to "ON" and "OFF" only. Does not have "HOLD"
|
9/10/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Change Fire Service Phase II key switch to "ON" and "OFF" only. Does not have "HOLD" operation.
|
12/5/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
x
|
|
At some point the elevator control operating panel (cop) has been replaced. At the time of installation this elevator was required to have either a audio or visual signal indicating when the phase 1 fireman service operation was activated. Install either an audio or visual signal to activate with fireman service phase I operation.
|
12/5/2023
|