Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect Yes No Car emergency telephone does not work. Needs to be programmed to a 24 hour source. 2/20/2019
conversion conversion n/a No No Fix the oil leak either on the valve or pump, or both. 4/19/2019
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 No No Repair oil leaks under the tank. 7/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No No maintenance control program. Provide electrical prints for controller. 7/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No No fire extinguisher in machine room. 7/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. 12/18/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Need fire extinguisher in machine room 9/3/2021
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Change Fire Service Phase II key switch to "ON" and "OFF" only. Does not have "HOLD" 9/10/2021
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal Yes No At some point the elevator control operating panel (cop) has been replaced. At the time of installation this elevator was required to have either a audio or visual signal indicating when the phase 1 fireman service operation was activated. Install either an audio or visual signal to activate with fireman service phase I operation. 12/5/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Change Fire Service Phase II key switch to "ON" and "OFF" only. Does not have "HOLD" operation. 12/5/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Yes No Machine room door shall be kept closed and locked. Door shall be self closing and self locking 5/13/2025
MO Minimum : Elevators (A) - Hoistways (A)13 No No Close hoistway wall penetrations 2/15/2026
MO Minimum : Elevators (A) - Hoistways (A)13 No No Holes in overhead shall be sealed (previously a traction elevator) 2/15/2026
MO Minimum : Elevators (A) - Hoistways (A)13 No No Repair the ventilation cover at the top of the hoistway 2/15/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No A light fixture in the elevator cab was not operational on the day of inspection. Repair light fixture to provide adequate lighting. 2/15/2026
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No Hole in Machine Room wall shall be repaired 2/15/2026
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine Room door shall be self closing and self locking. Needs knob and lock. 2/15/2026
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key. 2/15/2026
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. 2/15/2026
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Machine Room lights shall be installed per NEC and provide 10 foot candles 2/15/2026
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No The lighting in the elevator machine room is not sufficient. The lighting shall not be less than (10) foot candles at the floor level. 2/15/2026
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No Fire Service module in machine room shall be properly mounted. 2/15/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Pit shall be cleaned (oil) 2/15/2026
MO Minimum : Elevators (I) - Pits (I)1 No No The elevator pit floor is covered in dust and debris. The pit shall be cleaned. 2/15/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Clean Elevator pit 2/15/2026
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 No No The belts on the hydraulic pump motor are mismatched and worn unevenly. Replace belts for a smooth operation of pump to motor. 2/15/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No There is no fire extinguisher in the machine room, as required. Provide an ABC type extinguisher of proper size for the room. 2/15/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire Extinguisher shall be kept up to date 2/15/2026
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Pit access door shall be kept closed and locked 2/15/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces No No Remove unnecessary materials from the machine room 2/15/2026
A17.1-2016 : Elevators 4.2 - Hoistway doors 2.11 Yes No Transition between the landing sill and the tile/carpet exceeds 1" and creates a trip hazard. Floor transition shall be beveled or decreased to less than 1/4" 3/25/2026