Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting A light fixture in the elevator cab was not operational on the day of inspection. Repair light fixture to provide adequate lighting.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers There is no fire extinguisher in the machine room, as required. Provide an ABC type extinguisher of proper size for the room.
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The lighting in the elevator machine room is not sufficient. The lighting shall not be less than (10) foot candles at the floor level.
MO Minimum : Elevators (H) - Machine Rooms (H)4 The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed.
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit floor is covered in dust and debris. The pit shall be cleaned.
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 The belts on the hydraulic pump motor are mismatched and worn unevenly. Replace belts for a smooth operation of pump to motor.
MO Minimum : Elevators (H) - Machine Rooms (H)2 The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key.
MO Minimum : Elevators (I) - Pits (I)1 Clean Elevator pit
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Pit access door shall be kept closed and locked
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces Remove unnecessary materials from the machine room
conversion conversion n/a Fix the oil leak either on the valve or pump, or both. 4/19/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No maintenance control program. Provide electrical prints for controller. 7/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No fire extinguisher in machine room. 7/1/2020
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 Repair oil leaks under the tank. 7/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Need fire extinguisher in machine room 9/3/2021
MO Minimum : Elevators (A) - Hoistways (A)13 Close hoistway wall penetrations
conversion conversion conversion - reinspect x Car emergency telephone does not work. Needs to be programmed to a 24 hour source. 2/20/2019
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Change Fire Service Phase II key switch to "ON" and "OFF" only. Does not have "HOLD" operation. 12/5/2023
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal x At some point the elevator control operating panel (cop) has been replaced. At the time of installation this elevator was required to have either a audio or visual signal indicating when the phase 1 fireman service operation was activated. Install either an audio or visual signal to activate with fireman service phase I operation. 12/5/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 12/18/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x x Change Fire Service Phase II key switch to "ON" and "OFF" only. Does not have "HOLD" 9/10/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 x Machine room door shall be kept closed and locked. Door shall be self closing and self locking