Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)13 Close hoistway wall penetrations 2/15/2026
MO Minimum : Elevators (A) - Hoistways (A)13 Holes in overhead shall be sealed (previously a traction elevator) 2/15/2026
MO Minimum : Elevators (A) - Hoistways (A)13 Repair the ventilation cover at the top of the hoistway 2/15/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting A light fixture in the elevator cab was not operational on the day of inspection. Repair light fixture to provide adequate lighting. 2/15/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 12/18/2020
MO Minimum : Elevators (H) - Machine Rooms (H)1 Hole in Machine Room wall shall be repaired 2/15/2026
MO Minimum : Elevators (H) - Machine Rooms (H)2 x Machine room door shall be kept closed and locked. Door shall be self closing and self locking 5/13/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine Room door shall be self closing and self locking. Needs knob and lock. 2/15/2026
MO Minimum : Elevators (H) - Machine Rooms (H)2 The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key. 2/15/2026
MO Minimum : Elevators (H) - Machine Rooms (H)4 The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. 2/15/2026
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine Room lights shall be installed per NEC and provide 10 foot candles 2/15/2026
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The lighting in the elevator machine room is not sufficient. The lighting shall not be less than (10) foot candles at the floor level. 2/15/2026
MO Minimum : Elevators (H) - Machine Rooms (H)8 Fire Service module in machine room shall be properly mounted. 2/15/2026
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit floor is covered in dust and debris. The pit shall be cleaned. 2/15/2026
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be cleaned (oil) 2/15/2026
MO Minimum : Elevators (I) - Pits (I)1 Clean Elevator pit 2/15/2026
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 Repair oil leaks under the tank. 7/1/2020
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 The belts on the hydraulic pump motor are mismatched and worn unevenly. Replace belts for a smooth operation of pump to motor. 2/15/2026
MO Minimum : Elevators (S) - Fire Service (S)1 x x Change Fire Service Phase II key switch to "ON" and "OFF" only. Does not have "HOLD" 9/10/2021
A17.1-2016 : Elevators 4.2 - Hoistway doors 2.11 x Transition between the landing sill and the tile/carpet exceeds 1" and creates a trip hazard. Floor transition shall be beveled or decreased to less than 1/4"
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal x At some point the elevator control operating panel (cop) has been replaced. At the time of installation this elevator was required to have either a audio or visual signal indicating when the phase 1 fireman service operation was activated. Install either an audio or visual signal to activate with fireman service phase I operation. 12/5/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Change Fire Service Phase II key switch to "ON" and "OFF" only. Does not have "HOLD" operation. 12/5/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No maintenance control program. Provide electrical prints for controller. 7/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No fire extinguisher in machine room. 7/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Need fire extinguisher in machine room 9/3/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers There is no fire extinguisher in the machine room, as required. Provide an ABC type extinguisher of proper size for the room. 2/15/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire Extinguisher shall be kept up to date 2/15/2026
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Pit access door shall be kept closed and locked 2/15/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces Remove unnecessary materials from the machine room 2/15/2026
conversion conversion conversion - reinspect x Car emergency telephone does not work. Needs to be programmed to a 24 hour source. 2/20/2019
conversion conversion n/a Fix the oil leak either on the valve or pump, or both. 4/19/2019