Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Handrails need to be installed on top of car. 1 ft. gap between car top and back of hoistway. Side is open to other car. 2/24/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 x Machine room door shall be self locking and self closing. 3/1/2021
MO Minimum : Elevators (I) - Pits (I)5 x Install pit ladder and platform to work on cylinder head. 3/1/2021
MO Minimum : Elevators (I) - Pits (I)5 The pit shall have a permanently installed ladder. (Currently folding ladder)
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be cleaned. 2/24/2020
MO Minimum : Elevators (I) - Pits (I)5 x A permanent code compliant pit ladder shall be installed. (Repeat Violation) Re-Inspection now required. 10/18/2024
MO Minimum : Elevators (I) - Pits (I)5 x A permanent code compliant pit ladder shall be installed. (Repeat Violation) Re-Inspection still required and if not compliant possible red tag to be issued.
MO Minimum : Elevators (S) - Fire Service (S)1 x x Fire jewel not working. 3/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x Emergency light does not work. 3/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 3/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1.1.5 Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational on normal power and battery back-up. 3/24/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.3.1.2(c) Lighting in machine room is on a motion sensor in the hallway. Light needs to be on its own circuit. 8/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.35 - Supply Line and Shutoff Valve 3.19 Install shut off valve in the machine room. 2/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.37 - Pressure Switch 8.11.3.2.5 Pressure Switch (Re-Inspection) x Jack head is above the pump unit. Install pressure switch. 3/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.6.4.13.1(l) door restrictors x x Door restrictor does not work. Did not red tag. 7/30/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 8.11.2.1.3(b) Car top light does not work. 2/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.3 Guards Between Adjacent Pits Pit ladder needs to be mounted to the wall and not a free standing ladder. 8/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits The pit shall be kept clean. Clean the pit.
conversion conversion conversion - reinspect x Repair inoperative emergency lights. 9/24/2019
conversion conversion n/a Jack head is above the pump unit. Install pressure switch. 2/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.