Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Up to date operating certi?cate required in machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Pit shall be dry and clean. (full of water)
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone shall work.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency light shall work
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 Access to Pit No No Walk in pit door shall be locked at all times.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures No No Fire service module shall be cover.
conversion conversion conversion - reinspect Yes No Repair inoperative emergency lights. 9/24/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.3 - Operating control devices 8.11.2.1.1(c) No No Floor 1 call button is missing. 2/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.35 - Supply Line and Shutoff Valve 3.19 No No Install shut off valve in the machine room. 2/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 8.11.2.1.3(b) No No Car top light does not work. 2/24/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Handrails need to be installed on top of car. 2' gap between car top and back of hoistway. Side is open to other car. 2/24/2020
MO Minimum : Elevators (A) - Hoistways (A)3 No No 1st-6th floor doors need pick-up rollers. 2/24/2020
MO Minimum : Elevators (I) - Pits (I)1 No No Pit needs to be cleaned. 2/24/2020
conversion conversion n/a No No Jack Head is above the pump unit. Install pressure switch. 2/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.37 - Pressure Switch 8.11.3.2.5 Pressure Switch (Re-Inspection) Yes No Jack head is above the pump unit. Install pressure switch. 3/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. 3/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Emergency light does not work. 3/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) No No Lighting in machine room is on a motion sensor in the hallway. Light needs to be on its own circuit. 8/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 8.11.2.1.3(r) No No Wiring on car top needs to be in conduit. 8/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.3 Guards Between Adjacent Pits No No Pit ladder needs to be mounted to the wall and not a free standing ladder. 8/1/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational on main power and battery back-up. 3/24/2023
MO Minimum : Elevators (I) - Pits (I)5 Yes No A permanent code compliant pit ladder shall be installed. (Repeat Violation) Re-Inspection now required. 10/18/2024
MO Minimum : Elevators (I) - Pits (I)5 Yes No A permanent code compliant pit ladder shall be installed. (Repeat Violation) Re-Inspection still required. If not compliant, possible red tag to be issued. 12/20/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 4/7/2026
MO Minimum : Elevators (I) - Pits (I)5 No No Pit shall have a permanently installed ladder. (Currently folding ladder) 4/7/2026
MO Minimum : Elevators (I) - Pits (I)1 No No The pit shall be kept clean. Clean the pit. 4/7/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 4/7/2026