MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
|
|
1st-6th floor doors need pick-up rollers.
|
2/24/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
x
|
|
A permanent code compliant pit ladder shall be installed. (Repeat Violation) Re-Inspection now required.
|
10/18/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
x
|
|
A permanent code compliant pit ladder shall be installed. (Repeat Violation) Re-Inspection still required. If not compliant, possible red tag to be issued.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.2 - Car top light and outlet
|
8.11.2.1.3(b)
|
|
|
Car top light does not work.
|
2/24/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
Emergency light does not work.
|
3/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
3/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.3 - Operating control devices
|
8.11.2.1.1(c)
|
|
|
Floor 1 call button is missing.
|
2/24/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Handrails need to be installed on top of car. 2' gap between car top and back of hoistway. Side is open to other car.
|
2/24/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.35 - Supply Line and Shutoff Valve
|
3.19
|
|
|
Install shut off valve in the machine room.
|
2/24/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.37 - Pressure Switch
|
8.11.3.2.5 Pressure Switch (Re-Inspection)
|
x
|
|
Jack head is above the pump unit. Install pressure switch.
|
3/1/2021
|
conversion
|
conversion
|
n/a
|
|
|
Jack Head is above the pump unit. Install pressure switch.
|
2/24/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
|
|
Lighting in machine room is on a motion sensor in the hallway. Light needs to be on its own circuit.
|
8/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.3 Guards Between Adjacent Pits
|
|
|
Pit ladder needs to be mounted to the wall and not a free standing ladder.
|
8/1/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit needs to be cleaned.
|
2/24/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
|
|
Pit shall have a permanently installed ladder. (Currently folding ladder)
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Repair inoperative emergency lights.
|
9/24/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational on main power and battery back-up.
|
3/24/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit shall be kept clean. Clean the pit.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
8.11.2.1.3(r)
|
|
|
Wiring on car top needs to be in conduit.
|
8/1/2021
|