Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No The auxiliary power lowering operation shall be functional. (2nd Notice) 5/13/2025
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d No No All machine rooms or enclosures shall have a self-locking and self-closing door and shall be operable from the interior space without the use of a key. 5/5/2026
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Battery lowering unit is not operational. 5/9/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 5/5/2026
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 8/31/2021
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 8/31/2021