Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Inspection incomplete, the following items need to be performed to complete the inspection: Full speed buffer testing, full load testing of the car buffer, full load safety test, pull out, pull thru, spin the governor, fire service, earthquake, door pressure and 125% brake testing. Re-inspection required 5/12/2025
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Phase 2 fire service does not work, needs repair. Re-inspection required 1/30/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Seismic operation does not work as intended. When you activate seismic the buzzer goes off but the car doesn’t run into the floor zone and open door 2/9/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The following items shall be performed to complete the testing: Full speed buffer testing, full load testing of the car buffer, full load safety test, pull out, pull thru, spin the governor, fire service, earthquake, door pressure and 125% brake testing. Re-inspection required 6/2/2025