A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Emergency light not working.
|
2/24/2020
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)12
|
x
|
|
Test Fireman's recall
|
10/29/2019
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Emergency light shall work.
|
2/10/2020
|
A17.1-1996 : Elevators
|
5.10 - Compensating chains, ropes, and sheaves
|
1001.2(e)(8)
|
x
|
|
Shorten compensating ropes.
|
1/22/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher in machine room is expired, have serviced or replaced.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to perform the following tests to complete 5 yr inspection: counterweight buffer, counterweight safeties, car buffer, car safeties, 125% brake, both car & counterweight governor pull outs, pull thru's, speed switches & jaws. Re-inspection required
|
12/13/2023
|