A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)(12) -
|
|
|
Phase I fireman's recall key switch needs to be replaced.
|
10/29/2019
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Replace missing duct covers at top of hoistway
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to perform the following tests to complete 5 year inspections: counterweight buffer, counterweight safeties, car buffer, car safeties, 125% brake, both governor pull outs , pull thru's, speed switch and jaw tripping speeds. Re-inspection required
|
12/12/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm bell does not work, needs repaired or replaced. Re-inspection required
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency light and bell shall work.
|
10/29/2019
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Emergency light does not work.
|
2/10/2020
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
1001.2(a)(18)
|
x
|
|
Car door restrictor does not work. 30 days to repair and reinspect.
|
2/10/2020
|
A17.1-1996 : Elevators
|
1.13 - Emergency exit
|
204.1e
|
x
|
|
Emergency exit cover shall be secured with a chain of not less than 12". Re-inspection required
|
12/12/2023
|