Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to perform the following tests to complete 5 year inspections: counterweight buffer, counterweight safeties, car buffer, car safeties, 125% brake, both governor pull outs , pull thru's, speed switch and jaw tripping speeds. Re-inspection required 12/12/2023
MO Minimum : Elevators (A) - Hoistways (A)16 Replace missing duct covers at top of hoistway
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency alarm bell does not work, needs repaired or replaced. Re-inspection required
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) x Car door restrictor does not work. 30 days to repair and reinspect. 2/10/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency light and bell shall work. 10/29/2019
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) - Phase I fireman's recall key switch needs to be replaced. 10/29/2019
A17.1-1996 : Elevators 1.13 - Emergency exit 204.1e x Emergency exit cover shall be secured with a chain of not less than 12". Re-inspection required 12/12/2023
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency light does not work. 2/10/2020