A17.1-1996 : Elevators
|
2.29 - Car and counterweight safeties
|
205
|
x
|
x
|
Broken safety shoe.
|
5/3/2019
|
A17.1-1996 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
105.3c
|
|
|
Cable on counterweight dead end is not installed correctly in cable fastening device.
|
2/24/2020
|
A17.1-1996 : Elevators
|
1.8 - Door closing force
|
112.4(b)
|
x
|
|
Need to obtain door closing force.
|
5/3/2019
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Emergency light shall work.
|
2/10/2020
|
A17.1-1996 : Elevators
|
1.13 - Emergency exit
|
204.1e
|
x
|
|
Emergency exit cover shall be secured with a chain not more than 12" in length. Re-inspection required
|
12/11/2023
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Alarm bell shall work
|
2/12/2019
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to perform the following tests to complete 5 year inspections: counterweight buffer, counterweight safeties, car buffer, car safeties, 125% brake, both governor pull thru, pull outs, speed switch and jaw tripping speeds. Re-inspection required
|
12/11/2023
|