Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect x Alarm bell shall work 2/12/2019
A17.1-1996 : Elevators 2.29 - Car and counterweight safeties 205 x x Broken safety shoe. 5/3/2019
A17.1-1996 : Elevators 3.22 - Wire rope fastening and hitch plate 105.3c Cable on counterweight dead end is not installed correctly in cable fastening device. 2/24/2020
A17.1-1996 : Elevators 1.13 - Emergency exit 204.1e x Emergency exit cover shall be secured with a chain not more than 12" in length. Re-inspection required 12/11/2023
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency light shall work. 2/10/2020
A17.1-1996 : Elevators 1.8 - Door closing force 112.4(b) x Need to obtain door closing force. 5/3/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to perform the following tests to complete 5 year inspections: counterweight buffer, counterweight safeties, car buffer, car safeties, 125% brake, both governor pull thru, pull outs, speed switch and jaw tripping speeds. Re-inspection required 12/11/2023