A17.1-1996 : Elevators
|
2.17 - Drive machine brake
|
207.2b
|
x
|
x
|
Drive machine brake will not hold 125% of rated load.
|
4/17/2019
|
A17.1-1996 : Elevators
|
5.9 - Buffers and emergency terminal speed limiting devices
|
109.1
|
x
|
|
Test car buffer at rated speed with rated load.
|
4/17/2019
|
A17.1-1996 : Elevators
|
5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions
|
203
|
x
|
x
|
Test car safeties with rated load and speed.
|
4/17/2019
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)12
|
x
|
|
Test fire service.
|
4/17/2019
|
A17.1-1996 : Elevators
|
5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions
|
1001.2(e)(10)
|
x
|
x
|
Bottom post roller guide needs to be replaced. Did not red tag. Reinspect within 30 days. Did not Red Tag.
|
2/20/2020
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
1001.2(a)(18)
|
x
|
|
Car door restrictor shall work. Reinspect within 30 days.
|
2/20/2020
|
A17.1-1996 : Elevators
|
4.2 - Hoistway doors
|
110
|
|
|
Replace spirator on floor 18 hoistway door. Reinspect all items within 30 days.
|
2/24/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to perform the following tests to complete 5 year inspections: counterweight buffer, counterweight safeties, car buffer, car safeties, 125% brake, car & counterweight governor pull thru, speed switch and jaw tripping speeds. Re-inspection required
|
2/5/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm bell does not work, needs repaired or replaced. Re-inspection required
|
3/28/2025
|