Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 1001.2(e)(10) x x Bottom post roller guide needs to be replaced. Did not red tag. Reinspect within 30 days. Did not Red Tag. 2/20/2020
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) x Car door restrictor shall work. Reinspect within 30 days. 2/20/2020
A17.1-1996 : Elevators 2.17 - Drive machine brake 207.2b x x Drive machine brake will not hold 125% of rated load. 4/17/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency alarm bell does not work, needs repaired or replaced. Re-inspection required 3/28/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to perform the following tests to complete 5 year inspections: counterweight buffer, counterweight safeties, car buffer, car safeties, 125% brake, car & counterweight governor pull thru, speed switch and jaw tripping speeds. Re-inspection required 2/5/2024
A17.1-1996 : Elevators 4.2 - Hoistway doors 110 Replace spirator on floor 18 hoistway door. Reinspect all items within 30 days. 2/24/2020
A17.1-1996 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 109.1 x Test car buffer at rated speed with rated load. 4/17/2019
A17.1-1996 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 203 x x Test car safeties with rated load and speed. 4/17/2019
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)12 x Test fire service. 4/17/2019