Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Cylinder packing is worn and leaking, repair/ replace as needed.
MO Minimum : Elevators (I) - Pits (I)1 Observed standing water in the pit, confirm sump pump is working, if not-replace.
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and dry. The pit needs to be cleaned. 7/7/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Photo eye on the car door is functional during fire service recall. Photo eye must be overridden during fire service Phase 1 and 2. 3/19/2021
conversion conversion n/a Post current State certificate in machine room 4/18/2019
conversion conversion n/a Repair electric eye on front car door 4/18/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State certificate in machine room 4/18/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 7/7/2023