MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
7/7/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Cylinder packing is worn and leaking, repair/ replace as needed.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Observed standing water in the pit, confirm sump pump is working, if not-replace.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
|
|
Photo eye on the car door is functional during fire service recall. Photo eye must be overridden during fire service Phase 1 and 2.
|
3/19/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State certificate in machine room
|
4/18/2019
|
conversion
|
conversion
|
n/a
|
|
|
Post current State certificate in machine room
|
4/18/2019
|
conversion
|
conversion
|
n/a
|
|
|
Repair electric eye on front car door
|
4/18/2019
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit shall be kept clean and dry. The pit needs to be cleaned.
|
7/7/2023
|