Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 4.4 - Hoistway door locking devices 1001.2(d)(4) Yes No retiring cam does not work 2/16/2023
MO Minimum : Elevators (F) - Electrical Switches (F)9 Yes No Provide a working main line fused disconnect in the machine room , 15 day reinspection 3/9/2023
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Provide machine room lighting 2/28/2023
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Machine room shall be kept clean, remove dust from controller and floor 2/28/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display current operating certificate in machine room 2/28/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No Provide a MCP in machine room 2/28/2023