Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting x Lower demarcation light is not working. Re-inspection required
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(H) Lower demarcation lights inoperative, repair.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(I) Main line disconnect wiring is not an approved conduit in accordance with NFPA 70 section 620.21
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(I) Mainline disconnect wiring is not in approved conduit per NFPA 70 section 620.21
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.2 Escalator Step-to-Skirt Clearance x Provide step indexing test, record results. 5/18/2023