Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Provide lighting for the entire route to the machine room for safe access
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace deteriorated bushings on hoist rope hitch on top of car
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 Yes Yes Full load car safety test failed due to governor jaw malfunction. Repair governor jaws and retest pull through force and perform safety test with full load. Red tagged until repaired and reinspected. 2/5/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Traveling cable supports (kellum) are broken underneath elevator cab. 6/2/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Traveling cable supports are broken underneath elevator cab. 6/2/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Provide maintenance control program on-site. 6/2/2026