Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Safeties will not set with full load. Taken out of service until repairs are made. 2/5/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Repair emergency light. 6/22/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 2/5/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light & bell are not working. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace deteriorating car hitch isolation bushings.