Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting Yes No The demarcation light fixtures failed to illuminate and shall be repaired/ replaced. 7/22/2024
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(H) No No Replace light in lower pit area
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(A) No No Repair oil leak in drive machine. 4/7/2023
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting Yes No Repair demarcation lights on top and bottom egress. 7/20/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting Yes No Repair demarcation lights on top and bottom egress. 4/7/2023
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting Yes No Repair demarcation light on both ends. 7/15/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.1.4 Maintenance Records No No Provide written maintenance control program to include wiring diagrams to be kept on site. 3/31/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.1.4 Maintenance Records No No Provide on-site maintenance records.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning No No Perform unit cleandown. 3/31/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning No No Perform unit clean down. 3/31/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning No No Perform unit clean down.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning No No Perform unit clean down.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.2 Escalator Step-to-Skirt Clearance Yes No Perform step indexing test. 7/20/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Oil leak in drive. Oil tracks on steps. 3/31/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2 No No Need to repair oil leak on drive machine
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2 No No Need to repair oil leak on drive machine
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning No No Need to perform complete cleandown
conversion conversion n/a No No Maintain step/skirt performance index at or below code requirements, right -side. 3/31/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(H) No No Demarcation lights on both ends are out. 3/31/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning No No Cleanout top and bottom pit area
conversion conversion n/a No No Clean top and bottom pits. 3/31/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.1 - Machinery space access, lighting, receptacle, and condition 8.6.8.14 No No Clean out pit areas. Light out lower area. 3/31/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning No No Clean down top and bottom pit area. 3/31/2026
conversion conversion n/a No No Check gear box oil level and clean leakage from gear box onto motor/brake assembly, and steps. 3/31/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.4 - Drive machine and brake 8.11.4.2.4 Yes Yes Brake torque failed. 9/24/2020