A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.3.1.2(j)
|
|
|
out of date
|
|
A17.1-2016 : Elevators
|
2.5 - Housekeeping
|
8.11.3.1.2(h)
|
|
|
Remove unauthorized material and clean
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post certificate
|
|
A17.1-2016 : Elevators
|
4.2 - Hoistway doors
|
8.11.3.1.4(b)
|
x
|
|
Hostway door pick up rollers needs to be replaced
|
12/28/2021
|
A17.1-2016 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
8.11.3.1.1(r)
|
x
|
|
Door restrictor does not work
|
12/28/2021
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4 Instructions for Locating Maintenance Records
|
|
|
No maintenance records
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Clean Pit
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Must Provide and Maintain Machine room Fire Extinguisher 2.7
|
|
A17.1-2016 : Elevators
|
3.17 - Door and gate equipment
|
8.11.3.1.3(r)
|
|
|
Must replace missing or Broken Pick up rollers to maintain proper Door interlock operation. 3.17
|
|
A17.1-2016 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
8.11.3.1.1(r)
|
x
|
|
Must make Door restricting device operable. 8.11.3.1.1(r)
|
1/20/2022
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Must post current state operating Certificate in Elevator Machine Room.
|
|
A17.1-2016 : Elevators
|
2.5 - Housekeeping
|
8.11.3.1.2(h)
|
|
|
Must remove, and not store material, that is not part of the elevator in the machine room. 2.5
|
|
A17.1-2016 : Elevators
|
2.32 - Control Valve
|
8.11.3.1.2(t)
|
|
|
Must seal Leakage on Control valve in power unit. 2.32
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
Must provide and Maintain all required MCP documents.
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Must post current State operation Cert. 5.100(2)
|
|