MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
5.14 - Shut off valves in the pit have excessive corrosion that shall be addressed.
|
4/4/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
5.5 - The traveling cable is damaged and shall be replaced.
|
4/4/2019
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Seal hole at sprinkler piping penetration.
|
4/4/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Install a code data plate. The plate shall read: "Missouri Minimums"
|
7/1/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Emergency/standby power operation of the elevator shall be tested to complete the annual inspection.
|
5/6/2021
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Seal the hole in the hoistway where the sprinkler enters the hoistway. It is located between the 1st and 2nd floors.
|
7/1/2021
|