Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Car door restrictor does not work, Repair or replace restrictor. Re-inspection in 30 days 5/26/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Need to install correct capacity plate in elevator cab. Capacity plate states 2500 lbs, actual car capacity is 2000 lbs.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Suspension ropes are below minimum diameter, replace suspension ropes. Re-inspection required 1/21/2023
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) x Elevator car door restrictor is damaged and not working. Need to repair or replace door restrictor. Re-inspection required
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators connected to a standby or emergency generator shall be tested for operation on standby or emergency power. Re-inspection required 1/21/2023