Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Counterweight runby is 2". Shorten suspension ropes to provide 6" minimum of counterweight runby. Re-inspection required 1/21/2023