MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.11 Runby (Re-Inspection)
|
x
|
|
Counterweight runby is 2". Shorten suspension ropes to provide 6" minimum of counterweight runby. Re-inspection required
|
1/21/2023
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Emergency power did not connect to the elevators, needs repaired. Re-inspection required
|
2/24/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Elevators connected to a standby or emergency generator shall be tested for operation on standby or emergency power. Re-inspection required
|
1/21/2023
|