Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Replace deteriorating under car safety assembly bushings. 1/9/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Counterweight safety tension sheave nearing bottom of travel, raise sheave. 1/9/2023
MO Minimum : Elevators (A) - Hoistways (A)16 No No Replace first floor interlock box cover. 1/9/2023
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) No No Provide data tag for recent suspension rope replacement on machine room hitch plate. 1/9/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Replace under car safety assembly bushings. 1/9/2023
MO Minimum : Elevators (N) - Guide Rails (N)2 No No Replace bottom left counterweight roller guides. 2/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Fire extinguisher is out of date. 2/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No The OTIS MCP and documentation for 2021, 2022 & 2023 are missing. 10/15/2025
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Fire service testing must be documented monthly. 10/15/2025
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Fire service testing must be documented monthly. 4/1/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Emergency generator testing shall be performed. Re-inspection required 4/1/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Communication loss monitor operation shall be tested. 10/15/2025
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Rope gauge bottoms on #5 hoist rope between floors 10-11. Replace hoist ropes within 60 days from above date. 8/25/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually. 2/8/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Fire service operation shall be tested. 2/8/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Communication loss monitor operation shall be tested. 2/8/2025