Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light does not work 1/18/2024
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean. Remove excess debris.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Shorten hoisting cables. Runby shall be a minimum of 6 inches 4/15/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) The OTIS MCP and documentation for 2021, 2022 & 2023 are missing.
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Fire service testing must be documented monthly.