Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No need to remove oil pumpback unit from pit 6/24/2021
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 3.29 No No Label car top, pit, and inside car on operating panel “car #1”
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal Yes No fire service phase 1 visual and audible signals did not work on the car operating panel
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No emergency lights did not work, replace the battery
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No only one emergency light bulb worked, replace burnt out emergency light bulb 5/12/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No replace missing hoistway door gib on the top floor 5/12/2022