Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Alarm bell did not work on battery power
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records could not find Maintenance Control Program Documents (MMCP) in the machine room
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log fire service test log is not being filled out monthly
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Provide a fire extinguisher in elevator equipment control room near access door. 3/12/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Provide Maintenance Records Log 3/12/2020
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Repair machine room lights that are not working, required to have all the light fixtures working above the running equipment
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts replace counterweight roller guides, tires are crumbling 11/3/2020
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log The firefighters service test log is not being filled out monthly. 1/3/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records The Maintenance Control Program (MCP) On-Site documents are not in the machine room. 1/3/2022