Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)3 No No 3rd floor hoistway door closer needs to be adjusted, will not self close last two inches 10/27/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No 1st floor hoistway door closer needs to be adjusted, will not self close last two inches 10/27/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Yes Yes the brake stopped the rotation of the drive sheave and the Ropes slid over the drive sheave during the 125% brake test. Elevator slid onto the final limit, elevator red tagged until passes 125% test. Counterweight balance is around 35% Item 2.27.2.1(1)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Adjust relating on two speed hoistway doors to get a minimum of 1/2 inch overlap on the landing marked "1", currently there is less than that in overlap creating a pinch hazzard 3/12/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Provide Maintenance Records Log 3/12/2020
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Repair machine room lights that are not working, required to have all the light fixtures working above the running equipment 10/27/2025
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Yes No Repair machine room lights that are not working, required to have all the light fixtures working above the running equipment. repeat violation
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Replace missing pit light bulb 10/27/2025
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No replace burnt out pit light bulbs 1/3/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Could not find Maintenance Control Program (MCP) documents in the machine room 10/27/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No The Maintenance Control Program (MCP) On-Site documents are not in the machine room. 1/3/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No The firefighters service test log is not being filled out monthly. 1/3/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No the fire service test log in the machine room is not being filled out monthly 10/27/2025