MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
elevator is not running at rated speed with rated load. safety slide distance does not comply with minimum distance.
|
5/20/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
replace counterweight roller guides, tires are crumbling.
|
11/3/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Repair machine room lights that are not working, required to have all the light fixtures working above the running equipment
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
fire service phase 1 recall did not work, fire service light turned on in the car operating panel but the elevator did not return to the recall floor
|
3/28/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
could not find Maintenance Control Program Documents (MCP) in the machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
The Maintenance Control Program (MCP) On-Site documents are not in the machine room.
|
1/3/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
The firefighters service test log is not being filled out monthly.
|
1/3/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
fire service test log was is not being filled out monthly
|
|