MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)5
|
|
|
replace burnt out cab ceiling light bulbs
|
1/3/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Adjust relating on the bi parting hoisway doors on all 3 landings so that when the doors are pulled open when the car is away from the floor there is a maximum gap of 2 inch between panels and the electric contact on the interlock doesn't open
|
5/2/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Adjust relating on the bi parting hoisway doors on all 3 landings so that when the doors are pulled open when the car is away from the floor there is a maximum gap of 2 inch between panels and the electric contact on the interlock doesn't open
|
5/2/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
8.6.1.4 Provide Maintenance Records
|
5/20/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Repair machine room lights they are not working
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean the pit.
|
5/20/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
The Maintenance Control Program (MCP) On-Site documents are not in the machine room.
|
1/3/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
could not find Maintenance Control Program (MCP) documents in the machine room
|
|