Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light not working.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x The hold feature is not working on phase 2
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide MCP, or location of MCP in machine room. 10/29/2020
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Provide fire service testing log in machine room, and document monthly testing. 10/29/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light not working. 6/29/2021
MO Minimum : Elevators (H) - Machine Rooms (H)1 Keep access to machine room clear, no storage in front of machine room door. 6/29/2021
MO Minimum : Elevators (H) - Machine Rooms (H)1 Keep access to machine room clear, and free of obstructions. 8/30/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Provide up to date fire extinguisher in machine room. 8/30/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room. 8/30/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light not working. 8/30/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Provide guarding for overhead lighting in machine room. 8/30/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide MCP in machine room. 8/30/2022