Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 8/23/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 8/23/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No The emergency lowering device (ERU) shall be operational. 3/28/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. Yes No A new fire alarm panel with new smokes and heats was installed in 2018. The following deficiencies are noted: 1. When sprinklers are installed in elevator pits, automatic fire detection shall be installed to initiate elevator recall in accordance with 2.27.3.2.1(c) of A17.1 - 2013. Note: A water-flow switch shall be permitted to initiate elevator recall upon activation of a sprinkler installed at the bottom of the elevator hoistway (the elevator pit), provided the water-flow switch and pit sprinkler are installed on a separately valved sprinkler line dedicated solely for protecting the elevator pit, and the water-flow switch is provided without time-delay capability. (The code compliance of this item is being researched) 3/28/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. Yes No A new fire alarm panel with new smokes and heats was installed in 2018. The following deficiencies are noted: 2. Heat-sensing fire detectors shall be located on the ceiling not less than 4" from the side wall, or on the side walls between 4" and 12" from the ceiling. Note: The heat detector in the overhead and pit do not meet these requirements. (The code compliance of this item is being researched) 3/28/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. Yes No A new fire alarm panel with new smokes and heats was installed in 2018. The following deficiencies are noted: 3. Spot-type smoke detectors shall be located on the ceiling or, if on a side wall, between the ceiling and 12" down from the ceiling to the top of the detector. Note: The smoke detector in the overhead does not meet these requirements. (The code compliance of this item is being researched) 3/28/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) No No Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 8/23/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 8/23/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No All machine rooms or enclosures shall have a self-locking door and shall be operable from the interior space without the use of a key. 8/23/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No Battery lowering device does not work per code. Where auxiliary power lowering operation is installed or altered, it shall conform to 3.26.10. 5/11/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No 2-way communication device shall work with and without main power. The party that answers the phone shall give proper location. 3/14/2023