Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x 2-way communication device shall work with and without main power. The party that answers the phone shall give proper location. 3/14/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 8/23/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 8/23/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x A new fire alarm panel with new smokes and heats was installed in 2018. The following deficiencies are noted: 1. When sprinklers are installed in elevator pits, automatic fire detection shall be installed to initiate elevator recall in accordance with 2.27.3.2.1(c) of A17.1 - 2013. Note: A water-flow switch shall be permitted to initiate elevator recall upon activation of a sprinkler installed at the bottom of the elevator hoistway (the elevator pit), provided the water-flow switch and pit sprinkler are installed on a separately valved sprinkler line dedicated solely for protecting the elevator pit, and the water-flow switch is provided without time-delay capability. (The code compliance of this item is being researched) 3/28/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x A new fire alarm panel with new smokes and heats was installed in 2018. The following deficiencies are noted: 2. Heat-sensing fire detectors shall be located on the ceiling not less than 4" from the side wall, or on the side walls between 4" and 12" from the ceiling. Note: The heat detector in the overhead and pit do not meet these requirements. (The code compliance of this item is being researched) 3/28/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x A new fire alarm panel with new smokes and heats was installed in 2018. The following deficiencies are noted: 3. Spot-type smoke detectors shall be located on the ceiling or, if on a side wall, between the ceiling and 12" down from the ceiling to the top of the detector. Note: The smoke detector in the overhead does not meet these requirements. (The code compliance of this item is being researched) 3/28/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 All machine rooms or enclosures shall have a self-locking door and shall be operable from the interior space without the use of a key. 8/23/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 8/23/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Battery lowering device does not work per code. Where auxiliary power lowering operation is installed or altered, it shall conform to 3.26.10. 5/11/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The emergency lowering device (ERU) shall be operational. 3/28/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 8/23/2022