The Phase One three position key operated switch shall be provided at the designated level. The designated level is defined as the main floor or level that best serves the needs of emergence personnel for fire fighting or rescue purposes.
|
3/13/2019
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Elevators with fire service features shall comply with the edition of ASME A17.1 that the elevator was constructed to meet.
|
3/13/2019
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
System type smoke detectors shall be installed in each elevator lobby.
|
3/13/2019
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
All cars shall be provided with a Illuminated visual and audio signaling system which shall be activated to alert passengers that the car is returning to the designated level.
|