Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) x The car door restrictor shall work. 1/10/2020
A17.1-1996 : Elevators 1.3 - Operating control devices 1001.2(a)(3) Independent service does not keep the doors open. 1/10/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency lighting shall work. 1/10/2020
A17.1-1996 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 1002.3f x Repair the broken conduit on the car buffer switch. 1/10/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.2-211.8 x x Phase 2 fire service does not work. Phase 2 fire service shall be repaired and retested. 1/10/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)2 The car ceiling is about to fall down. Take corrective action to properly repair the car ceiling. 9/14/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Car & hoistway doors need to be adjusted for proper alignment and operation. 8/12/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 3/16/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency light inside car does not work. 10/16/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 10/16/2023
A17.1-1996 : Elevators 3.23 - Suspension rope 212 x Hoistway ropes are rouged and nearing the minimal allowable diameter and meet the criteria for replacement. 10/16/2023